Alpine® Smoke Fire-Storm® IMB Hurricane Door

Auto-Smoke Sealed Insulated Fire Doors

Product Features

  • High quality hurricane door designed to prevent the spread of smoke
  • Perimeter smoke seals standard
  • FM Approved fire doors
  • Roller smoke doors approved for stainless steel fire doors

  • Oversize UL label up to 56’x30′
  • Smoke-proof door built in accordance with requirements specified by Underwriters Laboratories Inc.
Quality Smoke Sealed Doors
Request A Quote

APPLICATION USE
Fire Protection, Smoke Control, Storm, Hurricane door.

BOTTOM BARS
Bottom Bars for these FM Approved Doors and Roller Smoke Doors can be Galvanized, Stainless Steel, Hot Rolled Steel, Powder Coated, Weather Strip , Brush/Smoke Seal, Pneumatic Edge, Electric Edge, Wireless Edge, Double Angle, Slide Lock.


BRACKET PLATES

Bracket Plates for this Smoke-Proof Door and Insulated Hurricane Door can be Hot Rolled A36, Stainless Steel, Galvanized, Powder Coated, Viscous Governor, Oscillating Governor, Fire Drop Charge, Charge Wheel, Motor Prep., Chain Gearing, Thru-Wall Drop Plate, Round Bracket, Square Bracket, Hex Bracket, Single Gear Reducer, Double Gear Reducer.

COUNTERBALANCE ASSEMBLY
Assembly for this Hurricane Door can be Hot Rolled A36, Galvanized, Stainless Steel, Torsion Spring, Kicker, Life Cycle 17.5M thru 400M, Collars, Welded Tabs, Taped Holes, Lock Shaft Collar, Keyed, Bolted.

CURTAIN OPTIONS
Curtains for these FM Approved Doors and Roller Smoke Doors can be Galvanized, Stainless Steel, Prime Painted Galvanized, Powder Coated, Stamped Endlock, Cast Endlocks, Windlock Option, Brass End Lock.

GUIDE MATERIAL
Guide Material for these Roller smoke doors and the insulated hurricane door can be Hot Rolled A36, Stainless Steel, Galvanized Steel, Powder Coated, Structural Angles, Roll Formed Angles, Brush/Smoke Seal, Chain Lock Box, Electric Interlock, Tube Mounting.

HOOD/COVER
Insulated Hurricane Door Hood/Cover can be Galvanized, Stainless Steel, Prime Painted, Powder Coated, Flame Baffle, Lintel Seal, Smoke Lintel Seal, Back Fascia, Tension Cover, Operator Cover, Round, Square, Hex, Side End Cap, Motor Cover, T.O.C. Cover, F.O.C. Cover, F.O.W. Cover.

MATERIAL STYLE
Material for FM Approved Doors can be 22 Gauge, 20 Gauge, 18 Gauge.

OPERATION OF DOOR
Operation of the Roller Smoke Doors can be Push-up, Chain, Motor, Hand Crank, Redi-Master, Redi-Hoist, Redi-Lift, Chain Gear Reducer, Redi- Release.

Call Alpine today to learn more about this insulated hurricane door!

Click Here for UL Labeled Smoke and Draft Control Assemblies

Disclaimer: All data provided on this website is to be used for information purposes only, and is subject to change without prior notice. Alpine shall not be liable for technical or editorial errors or ommisions contained herein, nor for direct, incidental, consequential or any other damages resulting from furnishing, performance, or use of this information, even if Alpine Overhead Doors, Inc. has been advised of the possibility of such damages in advance. See the additional disclaimer in our Terms of Use.

Alpine® Smoke Fire-Storm® IMB Smoke-Proof Door

Advanced Windstorm Resistant Insulated Fire Doors

Below you will find comprehensive storm door drawing details for our hurricane door featuring important operation details for using hand chain, hand crank, or motor operation. Click here to request a quote on these rolling doors. AutoCAD drawings and AutoCAD details for this smoke-proof door may be selected on the CAD FILES option to the right. The AutoCAD storm door drawing details for the hurricane door comply with 08360, 08400 & 08330 construction specs. The drawing details available for Alpine’s Smoke Fire-Storm® IMB rolling doors have several mounting options, including face mounted to steel, masonry, or between jamb mounted.

Alpine’s Smoke Fire-Storm® IMB smoke-proof door is a high quality fire door that is designed to prevent the spread of smoke. They are a hurricane door that is Dade County, Florida approved for high winds up to 187mph and Underwriters Laboratories Inc. for fire protection. This smoke-proof door is a combination of the features of the Redi-Storm® and Fire-Tite® rolling doors models.

To download Hurricane Door, Smoke-Proof Door – Storm Door Drawing Details(PDF), please click below.

Get Adobe Reader for Hurricane Door, Smoke-Proof Door - Storm Door Drawing Details, rolling doors

Hurricane Door, Smoke-Proof Door - Storm Door Drawing Details, rolling doors
Hurricane Door, Smoke-Proof Door - Storm Door Drawing Details, rolling doors
  • Between Jamb Mounted
  • Not available but may be mounted to I-beam or steel tubes

The Smoke Fire-Storm® rolling doors AutoCAD drawing details are for informational purposes. They may change at any time. The CAD detail and CAD drawing reflect the options that are available to the architects and engineers compiling an AutoCAD drawing to present to contractors.  The AutoCAD detail and AutoCAD drawing will be updated regularly. Alpine’s hurricane door is built to last.

Alpine’s Engineering team will help you determine the exact rolling doors that will meet your specifications and requirements. Alpine will guide you through every step with your hurricane door and smoke-proof door with our storm door drawing details. Alpine will design rolling doors that will bring years of usage.

Alpine’s hurricane door and smoke-proof door is tough enough to stand up to a lot of usage. These rolling doors are built to last.

Call Alpine today to find out which rolling doors are right for your building.

Disclaimer: All data provided on this website is to be used for information purposes only, and is subject to change without prior notice. Alpine shall not be liable for technical or editorial errors or ommisions contained herein, nor for direct, incidental, consequential or any other damages resulting from furnishing, performance, or use of this information, even if Alpine Overhead Doors, Inc. has been advised of the possibility of such damages in advance. See the additional disclaimer in our Terms of Use.

Alpine®Smoke Fire-Storm® IMB Roller Smoke Doors

Windstorm Resistant SmokeFire Doors

To download specifications please click below.

Specifications (PDF) Adobe Acrobat

Specifications (DOC) Microsoft Word

Model SMOKE FIRE-STORM IMB®
Insulated Slats
Fire-Tite Rolling Doors

NOTE: For specifications for FM approved doors, architects must choose from a variety of options. The standard choice will be shown first in plain text followed by the options shown in [brackets] (Example “Finish: Galvanized [Powder coated] [Baked enamel]”). The specifier must make the appropriate choices and delete the others (Example: “Finish: Powder coated”).

GENERAL

1.01 SUMMARY OF ROLLER SMOKE DOORS

A. This section includes: [Manual] or [Electric] operated, automatic closing, Insulated Windstorm Resistant Overhead Rolling Fire Door.

1. Successfully tested by Architectural Testing Institute (ATI) under Dade County protocols PA 201, PA 202, and PA 203 for a design load of + 60 psf.

2. Provide doors with Underwriter’s Laboratories, Inc. (UL) and Underwriter’s Laboratories of Canada (ULC) label for the fire rating classification. [4 hr.], [3 hr.], [1 ½ hr.], or [3/4 hr.] UL and ULC approved doors to be in accordance with both fire and windstorm resistant standards.

3. Design doors to withstand a windload of + 60 psf, 1.5 safety rating (Dade County equivalent to a normal +90 psf rating) for doors up to 20’8” x 30’. Provide compatible analysis certified by a Florida professional engineer for doors over 20’8” x 30’.

4. Manufacturer must be capable of providing certified Net Vertical and Net Horizontal reaction forces imposed on door jambs.

5. Quality manufacturer listed by the Texas Department of Insurance’s Windstorm Resistant Construction Guide and the Texas Windstorm Insurance Association Building Code for Windstorm Resistant Construction.

6. Cycle life: Design doors of standard construction for normal use of 10,000 cycles standard [up to 400,000 cycles].

7. Manually resetable drop out mechanism with optional release devices. (For automatically resetable doors see specs for Auto Fire-Storm®)

B. Related Sections: Related to this section, but not limited to, the following (based on Master Format 2004):

1. Section 01660 – Product Storage and Handling Requirements.

2. Section 04220 – Concrete Unit Masonry.

3. Section 05120 – Structural Steel.

4. Section 06100 – Rough Carpentry.

5. Section 08310 – Access Doors and Panels.

6. Section 08710 – Door Hardware.

7. Section 09290 – Gypsum Board.

8. Section 09900 – Paints and Coatings.

9. Section 26000 – Electrical.

10. Section 28310 – Fire Detection and Alarm.

1.02 REFERENCES FOR FM APPROVED DOORS

A. ASTM A 653/A 653M – Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process

B. ASTM A 36 – Standard Specification for Carbon Structural Steel, Hot Rolled Steel

C. ASTM A 123 – Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel Products

D. ASTM A 312 – Standard Specification for Seamless, Welded, and Heavily Cold Worked Austenitic Stainless Steel Pipes

E. ASTM A 240 – Standard Specification for Chromium and Chromium-Nickel Stainless Steel Plate, Sheet, and Strip for Pressure Vessels and for General Applications

F. ASTM A 276 – Standard Specification for Stainless Steel Bars and Shapes

G. ASTM A 31 – Standard Specification for Steel Rivets and Bars for Rivets, Pressure Vessels

H. ASTM A 449 – Standard Specification for Quenched and Tempered Steel Bolts and Studs

I. ASTM E 330 – Standard Test Method for Structural Performance of Exterior Windows, Doors, Skylights and Curtain Walls by Uniform Static Air Pressure Difference

J. Dade County PA-201, PA-202, PA-203: Large Missile Impact Test, Cyclic Wind Pressure Test, and Uniform Static Air Pressure Test

K. ASCE 7-93 – Standard Minimum Design Loads on Buildings and Other Structures

L. ASTM C 665 – Standard Specification for Mineral-Fiber Blanket Thermal Insulation for Light Frame Construction and Manufactured Housing

M. ASTM E 84 – Standard Test Method for Surface Burning Characteristics of Building Materials

1.03 SUBMITTALS FOR ROLLER SMOKE DOORS

A. Submit under provisions of Section 01300.

B. Product Data: Provide manufacturer’s standard details and catalog data. Provide installation instructions.

C. Shop Drawings: Furnish shop drawings for architect’s approval. Include elevation, sections, and details indicating dimensions, materials, finishes, conditions for anchorage and support of each door.

D. Submit manufacturer’s recommended operation, troubleshooting, and maintenance instructions.

1.04 QUALITY ASSURANCE

A. Manufacturer: Rolling doors shall be manufactured by a firm with a minimum of five years experience.

B. Fire-Rated Assemblies: Provide all doors with fire resistance rating required to comply with governing regulations which are inspected, tested, listed and labeled by UL, complying with NFPA 80 for class of opening. Provide UL label permanently fasted to each fire door assembly. Door shall be tested under UL10B and ULC10B, and provided with a [4 hour] [3 hr.] [1 ½ hr.] [3/4 hr.] rating. Also Factory Mutual and NY MEA approved.

C. Single-Source Responsibility: Manufacturer shall provide doors, tracks, motors, and accessories for each type of door. Secondary components shall come from a source acceptable to the manufacturer of the primary components.

1.05 DELIVERY, STORAGE, AND HANDLING OF FM APPROVED DOORS

A. Deliver materials in original packaging supplied by manufacturer with intact labels. Store materials away from harmful environmental conditions and construction.

1.06 WARRANTY

A. Door Warranty: Provide one year written warranty from date of installation against deficiencies due to defects in materials or workmanship. Installer agrees to repair or replace any defects in materials or workmanship.

B. Project Warranty: Refer to Conditions of the Contract for project warranty provisions.

PART 2 – PRODUCTS

2.01 MANUFACTURER

A. Manufacturer: Alpine Overhead Doors, Inc.; 8 Hulse Road Suite 1S, East Setauket, NY 11733. Telephone 800-257-4634 or 631-473-9300. Fax 631-642-0800.

B. Model: SMOKE FIRE-STORM IMB® Windstorm Resistant Rolling Fire Door

2.02 MATERIALS FOR ROLLER SMOKE DOORS

A. Curtain:

1. Slats: Constructed of 7/8” thick interlocking, roll-formed Insulated Metal Backed (IMB) V7 slats. (Slat construction allows for dual coiling flexibility)

a) Slat/Back Cover Material:

i) Galvanized steel, G90 coating exterior (G60 interior), Structural Quality Grade C, as per ASTM A 653/ A 653 M

Finish (Can be different for exterior/interior): Galvanized [Powder coated] [Baked enamel] (Minimum coating conforming with Coating Designation G-01 is required)

– OR –

ii) ASTM 240 Stainless steel 300 series

Finish (Can be different for slat and back cover): [Mill finish #2B] [#4 satin finish]

b) Insulation: Flame retardant fiberglass and acoustical dampening insulation, ASTM C 665. Surface Burning Characteristics (per ASTM E 84 and UL 723): Flame Spread = 0, Smoke Developed = 0. [Polycrete]

i) Thickness: 7/8”

ii) R-Value: 8.0 (U-factor of 0.125) calculated using the ASHRAE Handbook of Fundamentals.Gauge: (Per manufacturer’s standard)

i) Doors up to 20’8” wide: Minimum 21 gauge as manufacturer standard [20, 18, 16 gauge].

ii) Doors up to 12’ wide: Minimum 22 gauge [20, 18, 16]

2. Endlocks and Windlocks:

a) Ductile cast iron, hot-dipped, galvanized endlocks riveted to each end of each slat with four Semi-tubular, Mushroom Head ¼” rivets to prevent lateral movement and to limit slat deflection and bending stress. [Windlocks are dependent on windload and increase resistance to curtain jamming]

3. Bottom Bar: Two roll formed steel angles of minimum 2”x2”x1/8”, designed to reinforce curtain bottom. (Size dependent on dimensions per manufacturer’s standard)

a) Material for FM Approved Doors:

i) Galvanized Steel as per ASTM A 653/ A 653 M

Finish: Gray shop prime [Powder Coated] [Baked Enamel]

– OR –

ii) ASTM 240 Stainless Steel 300 Series

Finish: [Mill finish #2B] [#4 satin finish]

b) Bolting:

i) 20’8” wide: ¼” bolts at 15” o.c.

ii) 12’ wide: ¼” bolts at 20” o.c.

c) Weather Stripping: Rubber astragal bolted between bottom angles (Dade County Approved).

B. Guides:

1. Guides shall be designed using structural steel angles with a minimum thickness of 3/16”, minimum 1 ¼” slotted connections, and removable bellmouth curtain stops to allow for curtain maintenance without removal of guides. Bellmouth stops shall be flush with guide groove.

a) Angles:

i) 20’8” wide: Wall angle 3 ½ x 3 ½ x 7/16”, inside angle 2 ½ x 2 ½ x 3/8”, outside angle 4 x 3 x ¼”.

ii) 12’ wide: Wall angle 2 ½ x 3 ½ x ¼”, inside angle 2 x 2 ½ x ¼”, outside angle 3 x 3 3/16” min

b) Bolting:

i) 20’8” wide: Minimum 5/8” bolts at no more than 9” o.c.

ii) 12’ wide: Minimum 1/2” bolts at no more than 15” o.c.

c) Material for Roller Smoke Doors:

i) ASTM A 36 Carbon Structural Steel

Finish: Gray shop prime coat [ASTM A 123 Galvanized] [baked enamel paint] [powder coated].

– OR –

ii) ASTM 276 Stainless Steel 300 Series

Finish: [Mill finish #2B] [#4 finish satin]

2. Smoke Seal: 1 ½” brush smoke gaskets.

C. Door Support Brackets and Mounting Plates:

1. Steel plate not less than 1/4” thick. Provide ball bearings at rotating support points. Bolt plates to wall mounting angles with minimum 1/2″ fasteners. Plate supports counterbalance assembly and forms end enclosures.

a) Material:

i) ASTM A 36 Carbon Steel:

Finish: Gray shop prime coat [ASTM A 123 Galvanized] [Baked enamel paint] [Powder coated].

– OR –

ii) ASTM 240 Stainless Steel 300 Series

Finish: [Mill Finish #2B]

D. Counterbalance Assembly: Torsion

1. Counterbalance assembly: Steel pipe barrel of a size capable of carrying a curtain load with a maximum deflection of 0.03” per foot of door width. Heat-treated helical torsion springs encased in a steel pipe and designed to include an overload factor of 25% to ensure minimum effort to operate. Sealed and prelubricated high speed ball bearing at rotating support points. Torsion spring charge wheel for applying spring torque and for future adjustments.

a) Material for FM Approved Doors:

i) ASTM A 36 Carbon Structural Steel

Finish: Gray shop prime coat [A 123 Hot-Dip Galvanized]

– OR –

ii) A 312 Stainless Steel 300 Series Finish: Mill finish

b) Life Cycle: High Cycle springs designed to satisfy 10m through 400m life cycles. Consult engineering if height exceeds width for any cycle above 20m. (Cycle defined as one time opening and closing of door)

E. Hood:

1. 24 gauge steel. Formed to fit the contour of the end brackets with reinforced top and bottom edges. Provide support bracing for doors wider than 20 feet at every 10 feet to prevent excessive sag. Fasten with minimum ¼” bolts at 10” o.c.

2. Shape: Hexagon [square] [round]

3. Material:

a) Galvanized Steel as per ASTM A 653/ A 653 M

Finish: [Baked enamel paint] [Powder coated]

– OR –

b) ASTM 240 Stainless Steel 300 Series:

Finish: [Mill finish #2B] [#4 satin finish]

4. [Fascia]: Galvanized [Stainless Steel], provided where areas behind door hood are open. Materials and finish same as hood.

5. Smoke Seal: Lintel 2” brush seal.

6. [Fascia]: Galvanized [Stainless Steel], provided where areas behind door hood are open. Materials and finish same as hood.

F. Locking for Roller Smoke Doors

1. Provide padlockable slide locks for latching and locking door on coil side bottom bar at each jamb extending into slots in guides. (Electric Interlocks recommended with motorized doors only)

2. Manual chain hoist: Provide padlockable chain keeper on guide.

2.03 OPERATION:

A. Opening/Closing: Manual push-up [Manual hand chain] [Manual hand crank] [Motor Operator].

B. Automatic closure is activated by fusible link [Fire Door Release Device].

C. [Manual hand chain]:

1. Provide chain hoist operator with endless steel chain, chain pocket wheel and guard, geared reduction unit, and chain keeper secured to guide.

D. [Manual hand crank]:

1. Provide crank hoist operator including crank gear box, steel crank drive shaft and geared reduction unit. Fabricate gear box to completely enclose operating mechanism and be oil-tight.

E. [Motor Operators]:

1. Choose ONE:

a) Medium-Duty, Alpine® Model Redi-Hoist™ driven by efficient V-belt primary drive with chain/sprocket secondary. Maximum ½ hp. For use on doors up to 10’ x 10’.

– OR –

b) Industrial-Duty, Alpine® Model Redi-Lift™ driven by heavy-duty V-belt with chain/sprocket secondary reduction. Optional auxiliary chain hoist. Maximum 1 hp. For use on doors up to 12’ x 12’.

– OR –

c) Heavy Industrial-Duty, Alpine® Model Redi-Master™ driven by heavy-duty worm gear in oil bath reduction. Standard auxiliary chain hoist. Standard ½ hp (maximum 3 hp)

2. [Sensing Edges] (For double angle bottom bar): For motorized doors, sensing edges allow door to go up in case of obstruction. [Pneumatic Edge] [Electric Edge] [Wireless Edge].

a) Colors: Gray [Yellow] [Black] [White] [Yellow with black stripes]

F. Release Devices:

1. Fusible link with chain system:

a) Activation: Melting of fusible link at 165° Fahrenheit. When automatic closing is activated, chain shall disengage causing door to close.

b) Closing speed controlled by Integral Oscillating governor [Viscous governor].

c) Average closing speed: No less than 6” per second and not more than 24” per second as per NFPA 80 Section 6, paragraph 4.1.5.

2. [Redi-Release™ Release Devices]: Electric Fail-Safe devices used in conjunction with fusible link. [Smoke detector] Choose ONE from either standard models or SS class:

a) Class 1: Manually operated system that can be tied into most fire alarm systems.

– OR –

b) Class 2: All the features of Class 1, with the additional capability to allow motor operation. If operator is chosen, an electrical edge is recommended.

– OR –

c) Class 3: All the features of Class 2 with the addition of standard Alpine Control Panel and Standard Electric Safety Edge. Allows door to automatically go up in case of an obstruction.

– OR –

d) Class 4: All the features of Class 3 with the addition of the Alpine Uninterrupted Power Supply (Battery backup) that is self-activating during a power outage.

– OR –

e) SS Class Model A: Includes independently adjustable delays of 10 seconds on alarm activations (10 sec. max. adjust) and 10 seconds on power loss (30 sec. max. adjust) with a hold/release rating of 40 lbs.

f) SS Class Model B: All the features of model A with:

i) The hold open/release device shall recognize that the door is in the closed position and where motor driven, be capable of sensing that power is available to the motor. The device may be wired to close on alarm.

ii) [Audible and visual annunciators]: To operate during alarm closing cycle.

g) SS Class Model B2: All the features of model B with:

i) 72-hour battery backup with low/no battery logic sounder.

ii) Sounder/Strobe annunciator: To sound during closure due to alarm or power loss.

h) SS Class Model C: All the features of model B2 with:

i) Bottom bar sensing edge.

ii) Remote test plate.

2.04 Mounting of FM Approved Doors:

1. Interior face mounted on prepared opening.

2. Interior mounted between jambs and under lintel in a prepared opening.

3. Exterior face mounted on prepared opening.

2.05 Fire Ratings for Roller Smoke Doors:

1. Underwriter’s Laboratories:

Doors are constructed to conform within requirements specified by Underwriters Laboratories, Inc. (UL) and Underwriter’s Laboratories of Canada (ULC). Doors are automatic and self-closing, Class (A) (B) (C) (D) or oversized certificate.

4 hour – Approved for doors with openings not exceeding 162 sq. ft. in area.

Class (A) – 3 hour approved for doors in dividing fire walls with openings not exceeding 120 sq. ft. in area

Class (B) – 1 ½ hour approved for doors, in vertical shaft openings not exceeding 120 sq. ft. in area.

Class (C) – ¾ hour approved for doors in corridor or room-partition opening not exceeding 120 sq. ft. in area.

Class (D) – 1 ½ hour approved for doors in exterior wall opening not exceeding 120 sq. ft. in area.

The oversize Certificate is authorized for rolling steel doors for the protection of openings in fire walls, vertical shafts, and exterior walls where the area exceeds 120 square ft., or for openings in the above locations when width or height exceeds 12 ft. The maximum dimensions for doors for standard fire protection provided with the

Oversize Door Certificate are not to exceed 56 ft. in width and 24 ft. in height.

2. Factory Mutual.

3. New York Materials, Equipment and Acceptance Division (MEA).

PART 3 – EXECUTION

3.01 EXAMINATION

A. Verify that dimensions are correct and project conditions are in accordance with manufacturer’s installation instructions; do not proceed with installation until unacceptable conditions have been corrected.

3.02 INSTALLATION OF FM APPROVED DOORS

A. Install units in accordance with manufacturer’s instructions.

B. Ensure that units are installed plumb and true, free of warp or twist, and within tolerances specified by manufacturer for smooth operation.

C. Preparation for opening and installation of fire door to be in strict compliance with NPFA-80.

3.03 FIELD TESTING

A. Test doors for regular operation and automatic closing. Proper authorities having jurisdiction must witness test and sign Drop Test Form.

3.04 DEMONSTRATION OF ROLLER SMOKE DOORS

A. Instruct the Owner’s personnel in correct operation and maintenance of units.

3.05 ADJUST AND CLEAN

A. Clean units in accordance with manufacturer’s instructions.

B. Restore slight blemishes in finishes in accordance with manufacturer’s instructions to match original finish. Remove and provide new units where repairs are not acceptable to the Architect.

Alpine® Redi-Release®

For Use with Fire-Tite®, Fire-Shut® and Fire-Storm® Doors

Fire Door Release, Release Devices, LM90 Model - Optional Features

The Solid State Securities time delay fire door release device is an optional feature for your fire resistant doors. Alpine® Redi-Release® is normally energized as a fail-safe device for fire doors, and incorporates state of the art electronic security control circuitry.

The Redi-Release series release devices are the ideal safety option for fire resistant doors. These devices are able to respond to emergency conditions generated by manual or automatic  initiating devices that are normally closed, and are designed to be used in conjunction with a temperature fuse link system. The Test-Release device features include time delay on alarm and power loss, motor voltage sensing, form C output, proximity/door edge input and trouble diagnostic capabilities. Check model label to be installed to verify applicable features.

CAUTION: As with all releasing device systems, maximum fire protection is provided when installed in accordance with factory specifications and used with fuse link systems. Fail-safe operation can only be provided when input power is applied.

LiftMaster Professional

For Motorized Doors – Electro-Mechanical OperatorsFire Door Release, Release Devices, LM90 Model - Optional Features

The AFCB fire door release device is designed to be used in conjunction with a standard commercial door operator to provide a fully automated door closing system. For use with motorized doors incorporating a reversing electric safety edge. This 120VAC device can power up to four smoke detectors and two horn/strobes or speaker/strobes. This system combines state-of-the-art functionality and advanced features typically found on special-order fire door operators.

LM21AFCB                                                      Owners Manuals

  • UL864 Revision 9 compliant
  • Programmable DIP switch delay setting – either 10, 20, 30 or 60 seconds delay of door release to permit passage clearance
  • Internal battery backup system
  • Motor voltage sensing monitors voltage to the operator and activates a mechanical door release upon loss of power to the operator.
  • Obstruction cycling – works in conjunction with the door’s electrical safety edge, reversing the door if an obstruction is encountered
  • Test keyswitch – permits floor-level testing of the system
  • Model LM21AAFCBVB – is equipped with a voice board to broadcast a prerecorded evacuation message

Non-Motorized Doors

Fire Door Release, Release Devices, LM90 Model - Optional Features

The XP fire door release device provides a fail-safe release mechanism for non-motorized doors and acts as an interface between the door and the fire alarm system. The device required 24VDC power from an approved UL1481 regulated power supply with battery backup, such as a fire alarm control panel. Therefore, installation will require coordination with a fire panel installer.

LM21XP                                                     Owners Manuals

  • UL864 Revision 9 compliant
  • Programmable DIP switch delay setting – either 10, 20, 30 or 60 seconds delay of door release to permit passageway clearance
  • Close door detection – prevents door release if the door is kept in the closed position and eliminates door reset service calls or potential system damage
  • On board diagnostic –  LEDs for early troubleshooting
  • Testing function – allows routine fire door testing without requiring activation of the central alarm system; easy reset function returns the device to a standby state

Non-Motorized Doors with Battery Backup Option

Fire Door Release, Release Devices, LM90 Model - Optional Features

Versatility allows the XPBB fire door release device to operate on 120VAC, 24VAC or 24VDC power sources. Internal battery backup allows the release device to stand alone from the fire alarm system and act independently in the event of a power outage. The system can provide 24VDC power for up to four smoke detectors and two horn/strobes, mounted on either side of the door. Programmable delay settings, close door detection, diagnostic LEDs, localized testing, and reset capabilities are also standard.

LM21XPBB                                                           Owners Manuals

  • UL864 Revision 9 compliant
  • Programmable DIP switch delay setting – either 10, 20, 30 or 60 seconds delay of door release to permit passageway clearance
  • Inputs for normally open –  2-wire or 4-wire detectors and 4-wire normally closed detectors
  • On board diagnostic –  LEDs for early troubleshooting
  • Trouble and alarm relays – for communication with the fire alarm control panel, if required
  • Audible trouble sounder – to indicate when the release device is not operational
  • Testing function – allows routine fire door testing without requiring activation of the smoke detector
  • Model LM21XPBBVB – is equipped with a voice board to broadcast a prerecorded voice evacuation message

Contact us today to find out which Alpine® solution is right for you!

3 Hour approved for a hurricane door in dividing fire walls with openings not exceeding 120 sq. ft. in area. • 1.5 Hour approved for an insulated hurricane door in vertical shaft openings not exceeding 120 sq. ft. in area. • .75 Hour approved for FM approved doors in corridor or room-partition opening not exceeding 120 sq. ft. in area. • 1.5 Hour approved for roller smoke doors in exterior wall opening not exceeding 120 sq. ft. in area.

The Fire-Storm® insulated hurricane door is a combination of the features of Alpine’s Redi-Storm® and Fire-Tite® models. These roller smoke doors are Dade County approved for high wind loads (up to 187 mph) as well as UL and FM approved for fire protection. This insulated hurricane door comes in galvanized or stainless steel and in a variety of different finishes.

Fire-Storm® hurricane door curtains are constructed of IMB-V7 insulated flat steel slats, and can be finished with powder coating or baked enamel finishes. Each insulated hurricane door is equipped with a 22 gauge steel hood formed to fit the contour of the end brackets and durable ductile iron windlock with 1/4″ semi-solid rivets. Our roller smoke doors have  supports and brackets that are all steel plates no less than 1/4″ thick. Alpine’s Torsion Counterbalance Assembly is state of the art, providing maximum security and ease of use of these FM Approved Doors.

Hurricane Door, Insulated Hurricane Door, FM Approved Doors, Roller Smoke

IMB-V7 Insulated Flat Slat

Hurricane Door, Insulated Hurricane Door, FM Approved Doors, Roller Smoke

Double Angle Bottom Bar with Brush Seals

Hurricane Door, Insulated Hurricane Door, FM Approved Doors, Roller Smoke

Structural Guide with Windbar and Brush Seals